User Manual
12 / 20
Siemens RDF800KN… CB1N3174en
Smart Infrastructure Touch Screen Flush-mount Room Thermostats with KNX Communications 2020-02-21
LCD display Parameter Range Factory setting
Functionality of X1
0: --- No function
1: Ext / Return Temp (AI)
2: H/C changeover (AI/DI)
3: Window open detect (DI)
4: Dew point sensor (DI)
5: Enable electr. Heater (DI)
6: Fault input (DI)
7: Monitor input (Digital)
8: Monitor input (Temp)
10: Presence detection (DI)
3
Functionality of X2 1
Operating action
of X1
Normal Open (NO)
Normal Close (NC)
Normal Open
(NO)
Operating action
of X2
- End of wizard -
If more details are required about parameters, refer to basic documentation P3174.
To re-load factory settings for all parameters, set parameter P71 to ON. Restart the
thermostat after reset, all LCD segments flash, indicating that the reset is correct.
3 seconds later, the thermostat is ready for commissioning by qualified HVAC staff.
The room thermostats are delivered with a fixed set of applications. Select and
activate the relevant application during commissioning using one of the following
tools:
- Local DIP switch and HMI
- Synco ACS
- ETS5
Connect the Synco ACS or ETS5 tools to the KNX bus cable at any point for
commissioning:
ACS and ETS5 require an interface:
- Ethernet/LAN KNX interface (such as Siemens N148 / N146 / N152)
- OCI702 USB - KNX interface
An external KNX bus power supply is required if an RDF800KN... is connected
directly to a tool (ACS or ETS5) via KNX interface.
Reset
Ap
plications
Connect tool
Note: