Operating Instructions

14 CE1B3174.4xx, V4.0
User Level Control Parameters
FUNCTION
DESCRIPTIONS
RANGE
FACTORY
SETTINGS
P01
Control Sequence
(RDF800… only)
0: Heating only
1: Cooling only
2: Manual changeover
3: Auto changeover
4: Heating and Cooling
2-pipe = 1
4-pipe = 4
P02
User Operating Mode
Profile
1: COMF > PROT
2: COMF > ECON > PROT
1
P04
Selection of C or F
0: C
1: F
0
P05
Sensor Calibration
-3…3 K
0 K
P06
Standard Display
0: Room temperature
1: Setpoint
0
P07
Display Info Line
(2
nd
Line of LCD
Display)
0: --- (No display)
3: Time of day (12h) via bus
4: Time of day (24h) via bus
0
P08
Comfort Setpoint
5…40 C
21 C
P09
Comfort Min. Setpoint
5…40 C
5 C
P10
Comfort Max. Setpoint
5…40 C
35 C
P11
Econ Heating Setpoint
OFF, 5...WcoolEco
WcoolEco = 40°C Max.
15 °C
P12
Econ Cooling Setpoint
(RDF800… only)
OFF, WheatEco...4C
WheatEco = 5°C Min.
30 °C