Data Sheet for Product

2 / 20
Siemens RDF800KN… CB1N3174en
Smart Infrastructure Touch Screen Flush-mount Room Thermostats with KNX Communications 2021-04-22
Use
Room temperature control (heating or cooling) in individual rooms and zones by
means of:
2-pipe fan coil units
2-pipe fan coil units with electrical heater
4-pipe fan coil units
Chilled /heated ceiling
Chilled /heated ceiling and electrical heater
Chilled ceiling and radiator / under floor heating
Compressors in DX-type equipment
Compressors in DX-type equipment with electrical heater
The RDF800KN... controls:
One single or 3-speed fan
One or two ON/OFF valve actuators
One ON/OFF valve actuator and one 1-stage electrical heater
One 3-position valve actuator
One 1-stage compressor in DX-type equipment, or one 1-stage compressor with
electrical heater
Used in systems with:
Heating or cooling mode
Automatic heating/cooling changeover
Manual heating/cooling changeover
Heating and cooling mode (such as 4-pipe system)
The room thermostats are delivered with a fixed set of applications. The relevant
application is selected and activated during commissioning using one of the
following tools:
Synco ACS
ETS5
Local DIP switch and HMI
Functions
Room temperature control via built-in temperature sensor or external room
temperature / return air temperature sensor
Changeover between heating and cooling mode (automatically via local sensor
or bus, or manually)
Selection of applications via DIP switches or commissioning tool
Selection of operating mode via touch screen
Temporary Comfort mode extension
1- or 3-speed fan control (automatically or manually)
Display of current room temperature or setpoint in °C and/or °F
Minimum and maximum limitation of room temperature setpoint
Keylock function: unlock, total lock and setpoint
2 multifunctional inputs, freely selectable for:
Window contact
Presence detector
External room temperature or return air temperature sensor
Fault input
Monitor input for temperature sensor or switch state
Sensor for automatic heating / cooling changeover (RDF…)
Dew point sensor (RDF…)
Electric heater enable (RDF…)
Advanced fan control function, such as: fan kick, fan start delay, and selectable
fan operation (enable, disable or depending on heating or cooling mode)