Data Sheet for Product

13 / 22
Siemens RDF800… A6V101123362_en--_d
Smart Infrastructure Touch screen flush-mount standalone room thermostats 2019-10-29
Parameter
Name
Factory setting
Range
RDF800..
Dependencies
Expert level
P60
Periodic fan kick Comfort
OFF
0…89 min, OFF(90)
P52
P61
Periodic fan kick Eco
OFF
0…359 min, OFF(360)
P52
P62
Service filter
OFF (0)
OFF, 100…9900 h
P52
P65
Protection heating
setpoint
8 °C
OFF, 5…WCoolProt;
WCoolProt = 40 °C max.
P66
Protection cooling
setpoint
OFF
OFF, WHeatProt… 40;
WHeatProt = 5°C min.
P67
Fan start delay
0 s
0...360 s
P52,
P46
P69
Temporary Comfort
setpoint
OFF
OFF = disabled
ON = enabled
P71
Restore factory setting
OFF
OFF = disabled
ON = reload start
P77
Presence Detector Mode
1: Standard Presence
Mode
1: Standard Presence Mode
2: Hotel Presence Mode
P38,
P40
*)
Appl. = applications
Parameter
Name
Range
RDF800..
Dependencies
Diagnostics and
test
d01
Application number
NONE = (no application)
2P = 2-pipe
2P3P = 2-pipe 3-position
2PEH = 2-pipe with electric heater
4P = 4-pipe
d02
X1 state
0 = not activated (for DI)
1 = activated (DI)
0…49 °C = current temp. value (for AI)
00 = H/C input shorted
100 = H/C input open
d03
X2 state
0 = not activated (for DI)
1 = activated (DI)
0…49 °C = current temp. value (for AI)
00 = H/C input shorted
100 = H/C input open
d05
Test mode for checking
the Y1/Y2 actuator's
running direction
3)
"---" = no signal on outputs Y1 and Y2
OPE = output Y1 forced opening
CLO = output Y2 forced closing
P46
d07
Software version
Ux.xx
3)
This parameter can only be quit when the setting is back at “---
Press buttons + and simultaneously to escape.