Data Sheet for Product
13 / 22
Siemens RDF800… A6V101123362_en--_d
Smart Infrastructure Touch screen flush-mount standalone room thermostats 2019-10-29
Parameter
Name
Factory setting
Range
RDF800..
Dependencies
Expert level
P60
Periodic fan kick Comfort
OFF
0…89 min, OFF(90)
✓
P52
P61
Periodic fan kick Eco
OFF
0…359 min, OFF(360)
✓
P52
P62
Service filter
OFF (0)
OFF, 100…9900 h
✓
P52
P65
Protection heating
setpoint
8 °C
OFF, 5…WCoolProt;
WCoolProt = 40 °C max.
✓
P66
Protection cooling
setpoint
OFF
OFF, WHeatProt… 40;
WHeatProt = 5°C min.
✓
P67
Fan start delay
0 s
0...360 s
✓
P52,
P46
P69
Temporary Comfort
setpoint
OFF
OFF = disabled
ON = enabled
✓
P71
Restore factory setting
OFF
OFF = disabled
ON = reload start
✓
P77
Presence Detector Mode
1: Standard Presence
Mode
1: Standard Presence Mode
2: Hotel Presence Mode
✓
P38,
P40
*)
Appl. = applications
Parameter
Name
Range
RDF800..
Dependencies
Diagnostics and
test
d01
Application number
NONE = (no application)
2P = 2-pipe
2P3P = 2-pipe 3-position
2PEH = 2-pipe with electric heater
4P = 4-pipe
✓
d02
X1 state
0 = not activated (for DI)
1 = activated (DI)
0…49 °C = current temp. value (for AI)
00 = H/C input shorted
100 = H/C input open
✓
d03
X2 state
0 = not activated (for DI)
1 = activated (DI)
0…49 °C = current temp. value (for AI)
00 = H/C input shorted
100 = H/C input open
✓
d05
Test mode for checking
the Y1/Y2 actuator's
running direction
3)
"---" = no signal on outputs Y1 and Y2
OPE = output Y1 forced opening
CLO = output Y2 forced closing
✓
P46
d07
Software version
Ux.xx
✓
3)
This parameter can only be quit when the setting is back at “---“
Press buttons + and – simultaneously to escape.