Data Sheet for Product

8
Siemens
A6V12048672_en--_c
Smart Infrastructure
2021-05-17
Notes
Security
CAUTION
National safety regulations
Failure to comply with national safety regulations may result in personal injury and property
damage.
Observe national provisions and comply with the appropriate safety regulations.
Mounting and installation
Mount the room thermostat on the conduit box.
Do not mount on a wall in niches or bookshelves, behind curtains, above or near heat
sources, or exposed to direct solar radiation.
Mount about 1.5 m above the floor.
Mount the room thermostat in a clean, dry indoor place without direct airflow from a heat-
ing / cooling device, and not exposed to dripping or splash water.
Before removing the front cover, disconnect the power supply.
See Mounting Instructions A6V12064527 enclosed with the thermostat.
Wire, protect and earth in compliance with local regulations.
Adapt the line diameters to the rated value of the installed overcurrent protection device
as per local regulations.
Use only valve actuators rated for AC 230 V.
The AC 230 V mains supply line must have an external circuit breaker with a rated
current of no more than 10 A.
Isolate the cables of SELV inputs X1-M/X2-M, if the conduit box carries AC 230 V
mains voltage.
Inputs X1-M or X2-M of different units (e.g. summer/winter switch) may be connected
in parallel with an external switch. Consider overall maximum contact sensing current for
switch rating.
No metal conduits
No cables provided with metal sheathing.
Disconnect the thermostat from power supply before removing from the mounting
plate.
The device does not support hot-plug.
Mounting
Wiring