Data Sheet for Product

2
Siemens
A6V12048672_en--_c
Smart Infrastructure
2021-05-17
Use
Applications
Room temperature control in individual rooms and zones:
Heated or cooled with 2-pipe fan coil units
Heated or cooled with 2-pipe fan coil units with electrical heater
Heated and cooled with 4-pipe fan coil units
The room thermostat controls:
One ECM fan
One or two on/off valve actuators
One on/off valve actuator and one 1-stage electric heater
One 3-position valve actuator
One 1-stage compressor with electric heater
Used in systems with:
Heating or cooling
Automatic heating/cooling changeover
Manual heating/cooling changeover
Heating and cooling (e.g. 4-pipe system)
Functions
Maintain room temperature via built-in temperature sensor or external room tempera-
ture/return air temperature sensor
Automatic or manual changeover between heating and cooling
Select application via DIP switches
Select operating mode via operating mode button on the thermostat
ECM fan control (automatic or manual)
Display current room temperature or setpoint in °C and/or °F
Minimum and maximum setpoint limitation
Key lock (automatic and manual)
2 multifunctional inputs, freely selectable for:
External room temperature sensor or return air temperature sensor (AI)
Automatic heating/cooling changeover sensor (AI)
Window contact (DI)
Dew point sensor (DI)
Electrical heater enabled (DI)
Fault input (DI)
Monitor input (DI)
Monitor input (AI)
Automatic heating/cooling changeover sensor (DI)
Presence detector (DI)
Hotel keycard (DI)
Advanced fan control function, i.e. fan kick, fan start, selectable fan operation (enable,
disable or depending on heating or cooling)
Purge function together with 2-port valve in a 2-pipe changeover system
Reminder to clean filters
Floor heating temperature limit