Connection
Connection terminals
5
A6V12166490_en--_c
51 | 58
5 Connection
5.1 Connection terminals
L, N Operating voltage AC 230 V
Y50 DC 0...10 V fan output
M Reference for DC fan
Y1, Y2 Control output “Valve” AC 230 V (N.O., for normally closed valves),
output for compressor or output for electrical heater
X1, X2 Multifunctional input for temperature sensor (e.g. QAH11.1) or potential-
free switch
M Measuring neutral for sensor and switch
5.2 Connection diagrams
N1 Room thermostat
M1 DC 0...10 V fan
V1...V3 Valve actuator
E1 Electrical heater
S1 Switch (keycard, window contact,
etc.)
B1 Temperature sensor (return air
temperature, external room temperature,
changeover sensor, etc.)
C1, C2 Compressor