Functions
Control parameters
4
50 | 58
A6V12166490_en--_c
Parameter
Name
Factory setting
Range
Service level
d01
Application number
-
NONE = (No application)
2P = 2-pipe
2P3P = 2-pipe 3-position
2PEH = 2-pipe with electric heater
4P = 4-pipe
d02
X1 status
-
"---" = Function not selected
0 = Not activated (for DI)
1 = Activated (DI)
0…49 = Current temp. value (for AI)
-100 == Out-of-service (for AI)
00 = H/C Input shorted
100 = H/C Input open
d03
X2 status
-
"---" = Function not selected
0 = Not activated (for DI)
1 = Activated (DI)
0…49 = Current temp. value (for AI)
-100 == Out-of-service (for AI)
00 = H/C Input shorted
100 = H/C Input open
d05
Test mode for checking the Y1/Y2 actuator’s
running direction
-
0 = Output controlled by application
1 = 2-pipe on/off valve forced opening
2 = 2-pipe on/off valve forced closing
3 = 2-pipe 3-pos valve forced opening
4 = 2-pipe 3-pos valve forced closing
5 = 4-pipe heating valve forced opening
6 = 4-pipe heating valve forced closing
7 = 4-pipe cooling valve forced opening
8 = 4-pipe cooling valve forced closing
9 = Electrical heating valve forced opening
10 = Electrical heating valve forced closing
d06
Test mode for fan
-
0 = Output controlled by application
1 = Fan forced running
2 = Fan forced stop
d07
Software version
-
x.x.xx is displayed
Diagnostics and test