Functions
Control parameters
4
A6V12166490_en--_c
49 | 58
Parameter
Name
Factory setting
Range
Service level
3 = Cooling only
P54
Fan overrun time
60 s
0...360 s
P55
ECM fan max. output
80 %
ECM fan min…100 %
P56
ECM fan min. output
30 %
1%... ECM fan max.
P59
Fan minimum ON time
2 min
1...6 min
P60
Periodic fan kick Comfort
0
0 = Off or 1…89 minutes
90 = Fan continues to run
P61
Periodic fan kick Eco
0
0 = Off or 1…359 minutes
360 = Fan continues to run
P62
Fan filter service reminder
0
0 = Off or 100…9900 h
P65
Protection heating setpoint
8 ℃
0 = Off
5…WCoolProt (P66)
WCoolProt (P66)= 40 °C max.
P66
Protection cooling setpoint
0
0 = Off
WHeatProt (P65)…40
WHeatProt (P65) = 5 °C min.
P67
Fan start delay
0
0 = Off or 1...360 s
P68
Extension Comfort mode
0
0 = Off or 1...360 min
P69
Temporary Comfort setpoint
0
0 = Disable
1 = Enable
P70
Infrared receiver
1
0 = Disable
1 = Enable
P71
Restore factory setting
0
0 = Disable
1 = Reload start
P77
Time scheduler function
1
0 = Disable
1 = Enable