Functions
Control parameters
4
48 | 58
A6V12166490_en--_c
4.13.3 Expert level parameters with diagnostics and test
Parameter
Name
Factory setting
Range
Service level
P30
Heat P-band Xp/switching differential
2 K
0.5…6 K
P31
Cool P-band Xp/switching differential
1 K
0.5…6 K
P32
Integral time (fan)
0 min
0 …20 min
P33
Dead zone Comfort mode
2 K
0.5…5 K
P34
Setpoint differential
2 K
0.5…5 K
P35
Integral action time Tn
45 min
0...120 min
P36
H/C changeover switching point cooling
16 ℃
10…25 °C
P37
H/C changeover switching point heating
28 ℃
27…40 °C
P38
Input X1
3
0 = --- (no function)
1 = Room temp ext. sensor/ return air temp (AI)
2 = H/C changeover (AI)
3 = Window contact (DI)
4 = Dew point sensor (DI)
5 = Enable electric heater (DI)
6 = Fault input (DI)
7 = Monitor input (DI)
8 = Monitor input (AI)
9 = H/C changeover (DI)
10 = Presence detector (DI)
11 = Hotel keycard (DI)
P39
Normal position input X1
0
0 = Normally open/open
1 = Normally closed/close
P40
Input X2
1
0 = --- (no function)
1 = Room temp ext. sensor/ return air temp (AI)
2 = H/C changeover (AI)
3 = Window contact (DI)
4 = Dew point sensor (DI)
5 = Enable electric heater (DI)
6 = Fault input (DI)
7 = Monitor input (DI)
8 = Monitor input (AI)
9 = H/C changeover (DI)
10 = Presence detector (DI)
11 = Hotel keycard (DI)
P41
Normal position input X2
0
0 = Normally open/open
1 = Normally closed/close
P44
Actuator running time Y1/Y2
150 s
20…300 s
P45
Power of electric heater on Y2 (for adaptive
temperature compensation)
0
0.0...1.2 kW
resolution 0.1 Kw
P48
2-pos output minimum ON time
1 min
1...20 min
P49
2-pos output minimum OFF time
1 min
1...20 min
P50
Purge time
0
0 = Inactive or 1…5 minutes
P51
Floor heating temperature limitation
0
0 = Off or 10...50 °C
P52
Fan control
1
0 = Disabled
1 = Enabled
2 = Heating only