Functions
Multifunctional input, digital input
4
A6V12166490_en--_c
41 | 58
#
Function of input
Description
Type
X1/X2
10
Presence detector
The presence detector input switches the operating
mode to Comfort when the room is occupied and
returns to the previous operating mode when the room
is unoccupied. See also Hotel keycard/Presence
detector [➙ 27]
DI
11
Hotel keycard
The hotel keycard input switches the operating mode
to Economy with HMI locked when the room is
unoccupied and returns to the previous operating
mode when the room is occupied. See also Hotel
keycard/Presence detector [➙ 27]
DI
● The control action can be changed from normally open (NO) and normally
closed (NC) via parameter P39, P41.
● Each input X1 or X2 must be configured with a different function (i.e. 1…5 &
9…11). Exception: X1 or X2 input can be configured with same function (i.e. 6,
7, 8).
● X1 is factory-set to "Window contact" (3), X2 to "Room temperature external
sensor/return air temperature" (1).
If a multifunctional input is configured as analog: "Er3" is displayed when the output
is out of range (0...49 °C), open or shorted.
For detailed information, see Application overview [➙ 21].
● For inputs X1 and X2, one physical switch can be used for up to 20 thermostats
(parallel connection).
Caution! Do not mix X1 and X2.
● For sensors on inputs X1 or X2, the maximum cable length is 80 m.
Note