Basic Documentation

Table Of Contents
Functions
Control sequences
4
A6V12166490_en--_c
33 | 58
Heating and cooling mode (P01 = 4)
T[°C] Room temperature
w Room temperature setpoint
YH Control command "Valve"
(heating)
YC Control command "Valve"
(cooling)
SDH Switching differential "Heating"
(P30)
SDC Switching differential "Cooling"
(P31)
X
dz
Dead zone (P33)
Heating mode with manual selection
(P01 = 2) or
for energy saving (P09 ≥ P10) in
heating sequence
Cooling mode with manual selection
(P01 = 2) or
for energy saving (P09 ≥ P10) in cooling
sequence
Heating and cooling
4-pipe application with
manual changeover
On/Off control
Note