Functions
Control sequences
4
A6V12166490_en--_c
33 | 58
4.6.4 4-pipe fan coil unit
In 4-pipe applications, the thermostat controls 2 valves in heating and cooling
mode, heating/cooling by manual selection, or heating and cooling mode with
changeover. Heating and cooling (P01 = 4) is factory-set.
The heating or cooling output can be released via operating mode button if P01 is
set to Manual (P01 = 2).
The diagrams below show the control sequence for On/Off control.
Heating and cooling mode (P01 = 4)
T[°C] Room temperature
w Room temperature setpoint
YH Control command "Valve"
(heating)
YC Control command "Valve"
(cooling)
SDH Switching differential "Heating"
(P30)
SDC Switching differential "Cooling"
(P31)
X
dz
Dead zone (P33)
Heating mode with manual selection
(P01 = 2) or
for energy saving (P09 ≥ P10) in
heating sequence
Cooling mode with manual selection
(P01 = 2) or
for energy saving (P09 ≥ P10) in cooling
sequence
The diagrams only show the PI thermostat’s proportional part.
For setting sequence and control outputs, see Application overview [➙ 21],
Overview of sequences (setting via P01) [➙ 30] and Control outputs [➙ 36].
Heating and cooling
4-pipe application with
manual changeover
On/Off control
Note