Functions
Application overview
4
A6V12166490_en--_c
21 | 58
1)
Only required for heating and cooling applications (see Setpoints and sequences
[➙ 35])
● Setting the Comfort basic setpoint resets the runtime Comfort setpoint to the
basic setpoint.
● The resulting (current) setpoint for heating and cooling is limited by the
Protection setpoint; if the Protection setpoint is OFF, then minimum 5 °C and
maximum 40 °C are used.
● The resulting setpoints for cooling and heating of the same operating mode are
min. 0.5 K apart.
4.4 Application overview
The thermostats support the following applications, which can be configured using
the DIP switches on the front panel of the unit. Depending on the type, On/Off or
modulating control outputs are available.
General notes:
Notes on setpoint
adjustment