Functions
Room temperature setpoint
4
20 | 58
A6V12166490_en--_c
CAUTION
If a setpoint (Economy or Protection) is set to OFF, the thermostat does not
control the room temperature in the corresponding operating mode (heating or
cooling). As a result, there is no protective heating or cooling function and thus
risk of frost during heating or risk of overtemperature during cooling!
The Economy setpoints (P11, P12) can be accessed at the Service level;
Protection setpoints (P65, P66) at the Expert level.
4.3.2 Setting and adjusting setpoints
Room temperature setpoints can be:
● Set during commissioning
● Adjusted during runtime
The source can be following:
● Local HMI
The thermostat saves the setpoints to
● EEPROM in the form of parameters
The figure below shows the interrelation:
Room temperature:
Comfort setpoint