Functions
Operating modes
4
18 | 58
A6V12166490_en--_c
The operating mode is selected locally via the operating mode button.
The behavior of the operating mode button (user profile) can be defined via P02,
factory setting is P02 = 3.
P02
Without time
schedule
With time schedule
Description
1
⇨
⇨ ⇨
● Switching manually between 2 modes,
Economy is not available (factory setting)
● Suited for commercial buildings
● If a time schedule is available, then Comfort
can be temporarily extended (see Different
ways to influence the operating mode [➙ 18])
2
⇨ ⇨
⇨ ⇨ ⇨
● Switching manually between 3 modes
● Suited for homes and rooms where manual
switching to Economy is desired
● If a time schedule is available, then the Comfort
can be temporarily extended (see Different
ways to influence the operating mode [➙ 18])
3
⇨
⇨
● Switching manually between 2 modes,
Economy is not available (factory setting)
● Suited for hotel guest rooms or commercial
buildings
4
⇨ ⇨
⇨ ⇨
● Switching manually between 3 modes
● Suited for homes and rooms where manual
switching to Economy is desired
The thermostat is forced into Protection when the window is open. The contact can
be connected to multifunctional input X1 or X2. Set P38 or P40 to 3. User
operations are ineffective when window contact is active.
Only one input source must be used, either local input X1 or X2.
The operating mode can be changed to Comfort or Economy based on room
occupancy (room occupied or unoccupied, via presence detector or keycard).
For details, see Hotel keycard/Presence detector [➙ 27]
Comfort mode can be temporarily extended (e.g., working after business hours or
on weekends) when the thermostat is in Economy.
1. Press the operating mode button to return to Comfort for the preset period
(P68).
2. Press the operating mode button again to stop the schedule.
The following conditions must be fulfilled:
● Mode selection via operating mode button is set to "Auto-Comfort-Protection"
(P02 = 1) or "Auto-Comfort-Economy-Protection" (P02 = 2)
● P68 (extend Comfort period) is greater than 0
During the temporary Comfort extension, symbol is displayed.
When P68 (extend Comfort period) equals 0, extended Comfort cannot be
activated; pressing the left button switches the thermostat to Protection.
Availability of Economy
mode
Window contact
Note
Presence detector
Temporary timer to
extend Comfort mode