Data Sheet for Product

8
Siemens
A6V12005486_en--_c
Smart Infrastructure
2021-05-17
Mounting and installation
Mount the room thermostat on a recessed square conduit box with 60 mm fixing centers.
Do not mount on a wall in niches or bookshelves, behind curtains, above or near heat
sources, or exposed to direct solar radiation.
Mount about 1.5 m above the floor.
Mount the room thermostat in a clean, dry indoor place without direct airflow from a heat-
ing / cooling device, and not exposed to dripping or splash water.
In case of limited space in the conduit box, use mounting bracket ARG70.3 to increase
the headroom by 10 mm.
See Mounting Instructions A6V12060783 enclosed with the thermostat.
Comply with local regulations to wire, protect and earth the thermostat.
The device has no internal fuse for supply lines to fan and actuators. To avoid risk of
fire and injury due to short-circuits, the AC 230 V mains supply line must have a circuit
breaker with a rated current of no more than 10 A.
Properly size the cables to the thermostat, fan and valve actuators for AC 230 V
mains voltage.
Use only valve actuators rated for AC 230 V.
Adapt the wiring cross section for power supply (L, N), and 230 V outputs (Yx-N) to
the preceding overload protection elements (max 10 A) under all circumstances. Comply
with local regulations under all circumstances.
Cables of SELV inputs S1 (X2)-M / B1 (X1)-M: use cables with min 230 V insulation,
as the conduit box carries AC 230 V mains voltage.
Inputs S1 (X2)-M / B1 (X1)-M: several switches (e.g. summer/winter switch) may be
connected in parallel. Consider overall maximum contact sensing current for switch rat-
ing.
Selectable relay function: Follow the instructions in Basic documentation A6V12114068
to connect external equipment to the relay outputs.
Isolate the cables of Modbus communication input A+, B- and REF for 230 V.
Disconnect thermostat from power supply before removing from the mounting plate.
The device does not support hot-plug.
Mounting
Wiring