Functions
Room temperature setpoint
4
A6V12114068_en--_c
21 | 66
1)
Only required for heating and cooling applications (see Setpoints and sequences
[➙ 37])
The current setpoint (used by the thermostat for temperature control) is available
on the Modbus for use in the central control unit.
● Changes via the local HMI or tool have the same priority (last one always
wins).
● Setting the Comfort basic setpoint resets the runtime Comfort setpoint to the
basic setpoint.
● The resulting (current) setpoint for heating and cooling is limited by the
Protection setpoint; if the Protection setpoint is OFF, then minimum 5 °C and
maximum 40 °C are used.
● The resulting setpoints for cooling and heating of the same operating mode are
min. 0.5 K apart.
Room temperature:
Current setpoint
General notes:
Notes on setpoint
adjustment