Technical data
Power supply
Operating voltage AC 230 V (+10%, -15%)
Frequency 50/60 Hz
Power consumption Max. 12 VA
Internal fuse (replaceable)
Fuse type SLOW-BLOW
Size dia. 5.2x20 mm
Voltage rating 250 V
Current rating 6.3 A
Outputs
Valve output (RDF510) Y12 (N.C.)/Y14 (N.O.)
Rating
AC 230 V
5 mA…4(2) A
Valve output (RDF530) Y1 (N.O.) /Y2 (N.O.)
Rating
AC 230 V
5 mA…4(2) A
Fan output (3-speed fan) Q1, Q2, Q3
Rating
AC 230 V
5 mA…4(2) A
Operational data
Switching differential
- Heating mode
- Cooling mode
0.5...6 K (factory setting: 1 K)
0.5...6 K (factory setting: 1 K)
Setpoint setting range (see note below)
- Comfort mode
- Protection mode
5...40 °C
OFF, 5...40 °C
Built-in room temperature sensor
- Measuring range
- Accuracy at 25 °C
- Temperature calibration range
0…50 °C
< ±0.5 K
- 5.0...+5.0 K
Resolution of settings and display
- Temperature setpoints
- Current temperature value displayed
0.5 °C
0.5 °C
Note: The standard range is 5...40 °C. Customization is available upon request (e.g.
0…50 °C).
Ambient conditions and protection classification
Safety class II as per EN 60730-1
Pollution class II as per EN 60730-1
Degree of protection of housing IP30 as per EN 60529
Climatic ambient conditions
- Storage as per EN 60721-3-1
- Transport as per EN 60721-3-2
- Operation as per EN 60721-3-3
- Class 1K3
- Class 2K3
- Class 3K5
1)
1) No condensation is allowed.
Standards, directives and approvals
EU conformity (CE) A6V101090515
Environmental compatibility The product environmental declaration
(
A5W00085405A
) contains data on environmentally