Control parameters
Parameter Description Factory setting Setting range
P01 Control sequence RDF510 = 2
RDF530 = 4
0:= Heating only
1:= Cooling only
2:= H/C changeover manual
4:= Heating and cooling
(RDF530)
Note: RDF510: 0, 1, 2
RDF530: 2, 4
P05 Sensor calibration 0 K -5…+5 K
P06 Standard temperature display 0 0:= Room temperature
1:= Setpoint
P09 Minimum setpoint in Comfort mode 5 ℃ 5…40 ℃
P10 Maximum setpoint in Comfort mode 35 ℃ 5…40 ℃
P14 Keylock function 0 0:= No lock
1:= Full lock
2:= Partial lock
P15 Fan control deadzone in Comfort
mode
1 0:= Fan off
1:= Fan speed 1 in heating or
cooling mode
P27 Operating mode settings upon power
down
0 0:= Return to previous operating
mode or user settings
1:= Protection mode
2:= Comfort mode
P28 Timer with delay Off 0 0:= Users to set on-time duration
1 to 23:= Preset with a fixed on-
time in hours
P30 Switching differential in heating mode 1 K 0.5 … 6 K
P31 Switching differential in cooling mode 1 K 0.5 … 6 K
P33 Deadzone in Comfort mode 2 K 0.5 … 5 K (RDF530)
P59 Fan minimum On-time (dwelling time) 2 minutes 1…6 minutes
P65 Protection heating setpoint 8 ℃ OFF, 5 ℃…Wcool
pro
;
Wcool
pro
=40℃ max.
P66 Protection cooling setpoint OFF OFF, Wheat
pro
…40℃;
Wheat
pro
=5℃ min.
P71 Reload factory setting OFF OFF:= Disable
ON:= Reload start
“---” is displayed for 3 seconds
while reloading
P91
1)
Fan symbol display and function
controls - associated key button
function is disabled
RDF510 = 1
RDF530 = 1
0: disable display
1: enable display
P92
1)
H/C changeover symbol display and
function controls - associated key
button function is disabled
RDF510 = 1
RDF530 = 1
0: disable display
1: enable display
Notes:
1)
For RDF510/RDF530:
● If P91 = 0 is selected, P15, P59 will not be accessible by users;
● If P92 = 0 is selected,
– RDF510: P01 = 0 or 1, while the factory setting of P01 is 1 instead.
– RDF530: P01 = 4 only