Data Sheet for Product
Table Of Contents
14
Siemens
A6V10889950_en--_j
Smart Infrastructure
2022-01-05
Technical data
Power supply
Operating voltage
AC 230 V (+10%, -15%)
Frequency
50/60 Hz
Power consumption
Max. 12 VA
Internal fuse (replaceable)
Fuse type
SLOW-BLOW
Size
dia. 5.2x20 mm
Voltage rating
250 V
Current rating
6.3 A
Outputs
Valve output (RDF510) Y12 (N.C.)/Y14 (N.O.)
Rating
AC 230 V
5 mA…4(2) A
Valve output (RDF530) Y1 (N.O.) /Y2 (N.O.)
Rating
AC 230 V
5 mA…4(2) A
Fan output (3-speed fan) Q1, Q2, Q3
Rating
AC 230 V
5 mA…4(2) A
Operational data
Switching differential
- Heating mode
- Cooling mode
0.5...6 K (factory setting: 1 K)
0.5...6 K (factory setting: 1 K)
Setpoint setting range (see note below)
- Comfort mode
- Protection mode
5...40 °C
OFF, 5...40 °C
Built-in room temperature sensor
- Measuring range
- Accuracy at 25 °C
- Temperature calibration range
0…50 °C
< ±0.5 K
- 5.0...+5.0 K
Resolution of settings and display
- Temperature setpoints
- Current temperature value displayed
0.5 °C
0.5 °C
Note: The standard range is 5...40 °C. Customization is available upon request (e.g.