Control parameters
Parameter
Description
Factory setting
Setting range
P01
Control sequence
RDF510 = 2
RDF530 = 4
0:= Heating only
1:= Cooling only
2:= H/C changeover manual
4:= Heating and cooling (RDF530)
Note: RDF510: 0, 1, 2
RDF530: 2, 4
P05
Sensor calibration
0 K
-5…+5 K
P06
Standard temperature display
0
0:= Room temperature
1:= Setpoint
P09
Minimum setpoint in Comfort mode
5 ℃
5…40 ℃
P10
Maximum setpoint in Comfort mode
35 ℃
5…40 ℃
P14
Keylock function
0
0:= No lock
1:= Full lock
2:= Partial lock
P15
Fan control deadzone in Comfort mode
1
0:= Fan off
1:= Fan speed 1 in heating or
cooling mode
P27
Operating mode settings upon power down
0
0:= Return to previous operating
mode or user settings
1:= Protection mode
2:= Comfort mode
P28
Timer with delay Off
0
0:= Users to set on-time duration
1 to 23:= Preset with a fixed on-time
in hours
P30
Switching differential in heating mode
1 K
0.5 … 6 K
P31
Switching differential in cooling mode
1 K
0.5 … 6 K
P33
Deadzone in Comfort mode
2 K
0.5 … 5 K (RDF530)
P59
Fan minimum On-time (dwelling time)
2 minutes
1…6 minutes
P65
Protection heating setpoint
8 ℃
OFF, 5 ℃…Wcool
pro
; Wcool
pro
=40℃
max.
P66
Protection cooling setpoint
OFF
OFF, Wheat
pro
…40 ℃;
Wheat
pro
=5 ℃ min.
P71
Reload factory setting
OFF
OFF:= Disable
ON:= Reload start
“---” is displayed for 3 seconds while
reloading
P91
1)
Fan symbol display and function controls -
associated key button function is disabled
RDF510 = 1
RDF530 = 1
0: disable display
1: enable display
P92
1)
H/C changeover symbol display and
function controls - associated key button
function is disabled
RDF510 = 1
RDF530 = 1
0: disable display
1: enable display
Notes:
1)
For RDF510/RDF530:
● If P91 = 0 is selected, P15, P59 will not be accessible by users;
● If P92 = 0 is selected,
– RDF510: P01 = 0 or 1, while the factory setting of P01 is 1 instead.
– RDF530: P01 = 4 only