User Manual
7/16
Siemens Room Temperature Controllers N3067en
Building Technologies 2014-10-14
3. Symbol
1
will flash. Press + or - to select or deselect each day and advance to
the next day. Confirm setting for actual timer by pressing ok and advance to the
next timer.
1
The controller will leave the programmable timer setting mode if no button is pressed
within 20 seconds. All changes made after the last press of ok button will not be
saved.
Press the Prog button to sequentially review the 8 timers.
Timers A1…A4 have the following default setting:
Day/s
Time when controller is in Normal operation
Mo (1) – Fr (5) 06:30 – 08:30 (A1) 17:30 – 22:30 (A2)
Sa (6) 08:00 – 23:00 (A3)
Su (7) 08:00 – 22:30 (A4)
- During the remaining time, controller is in Economy (Energy
saving) mode
- Timers A5…A8 are free, no default setting
The setting of these timers can be changed to suit individual needs. The default setting
can be reloaded any time:
1. Set the controller to Standby
.
2. Press + and - simultaneously for 3 seconds. Release them and, within 2 seconds,
press 2 times Prog.
Then, the display will show “8888“ during the reloading process.
In case two, or when several timer sequences overlap, the resulting output is the OR
combination of the normal operating mode time of all timers.
A1=09:00-22:00
A2=12:00-20:00
09:00
12:00
20:00
22:00
Resulting output = 09:00-
22:00
3058D04
The 7day-time clock supports the 12-hour and 24-hour format. The format is chosen
during setting of the time clock as follows:
1. Keep the button depressed until the time digits start to flash and then press + or -
to set the time of day. If the current time is the 24-hour format and you wish to
change to the 12-hour format, press + passing 23:59 or press - passing 00:00. Vice
versa back to the 24-hour format.
2. Confirm the time of day by pressing ok and the weekday indicator starts to flash.
View the timers
Default timer setting
Reload default timer
setting
Overlapping of timer
sequences
7day-time clock