Siemens Room Temperature Controllers N3067en
Building Technologies 2014-04-04
Connection terminals solid wires or prepared
stranded wires
1x0.4-1.5 mm
2
Weight 0.17 kg
Color of housing front
white
, RAL 9003
*) The documents can be downloaded from http://siemens.com/bt/download.
Connection terminals
L
N Q1 Q2 Q3 Y11N
3057G01
AC 230 V
L, N Operating voltage AC 230 V
Q1 Control output “Fan speed 1 AC 230 V
Q2 Control output “Fan speed 2 AC 230 V
Q3 Control output “Fan speed 3 AC 230 V
Y11 Control output “Valve” AC 230 V (N.O.,
for normally closed valves) or output for
compressor
Connection diagrams
Application:
2-pipe fan coil units
L
N
10 A
L B1
M
N Q1 Q2 Q3 Y11N
4(2)A
max.
4(2)A
max.
I II III
A C 23 0 V
3
0
5
7
A
0
5
M1
V1
N1
AC 230 V
M1 3-speed fan
N1 Room temperature controller
RDF310.../RDF410...
V1 Zone valve
Application:
Compressor
in DX type equipment
L
N
1 0 A
L
N Q1 Q2 Q3 Y11N
4(2)A
max.
4(2)A
max.
I II III
A C 2 30 V
3
0
5
7
A
0
6
M1
C1
N1
AC 230 V
M1 3-speed fan
N1 Room temperature controller
RDF310.../RDF410...
C1 Compressor
General