User Manual
13/16
Siemens Room Temperature Controllers N3067en
Building Technologies 2014-10-14
Technical data
Operating voltage AC 230 V +10/-15 %
Frequency 50/60 Hz
Power consumption max. 8 VA
No internal fuse
External preliminary protection with max. C 10 A circuit breaker in the supply line
required under all circumstances
Fan control Q1, Q2, Q3-N
Rating
AC 230 V
5 mA…4(2)A
Control output Y11-N (N.O.)
Rating
AC 230 V
5 mA…4(2)A
Infrared receiver (only with RDF310.21 and RDF410.21)
Transmission distance
Orientation angle
≤ 7.5 m
≤ ± 30 °
Switching differential, adjustable from 0.5...4K
Heating mode (factory setting)
Cooling mode (factory setting)
2 K
1 K
Setpoint setting range
Normal operation
Economy (Energy saving) mode (RDF410..)
Standby
5...40 °C
off, 5...40 °C
off, 5...40 °C
Factory setting of setpoints
Normal operation
Economy (Energy saving) in heating / cooling
mode
Standby (heating and cooling mode)
20 °C
16 °C / 28 °C
OFF
Built-in room temperature sensor
Measuring range
Accuracy at 25 °C
Temperature calibration range
0…49 °C
< ± 0.5 K
± 3.0 K
Resolution of settings and display
Setpoints
Current temperature value displayed
0.5 °C
0.5 °C
Operation
Climatic conditions
Temperature
Humidity
to IEC 60721-3-3
class 3K5
0...+50 °C
<95 % r.h.
Transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
to IEC 60721-3-2
class 2K3
- 25...+60 °C
<95 % r.h.
class 2M2
Storage
Climatic conditions
Temperature
Humidity
to IEC 60721-3-1
class 1K3
- 25...+60 °C
<95 % r.h.
EU Conformity (CE) CE1T3067xx
*)
RCM Conformity CE1T3067en_C1
Devices of safety class II to EN 60730-1
Pollution class normal
Degree of protection of housing IP 30 to EN 60529
The product environmental declaration CE1E3067
*)
contains data on environmentally
compatible product design and assessments (RoHS compliance, materials
composition, packaging, environmental benefit, disposal).
Power supply
Outputs
Inputs
Operational data
Environmental
conditions
Norms and standards
Environmental
compatibility