To optimize the control performance, you can use local HMI to adjust a number of
control parameters. Proceed as follows to change the control parameter.
1. Set the thermostat to Protection mode .
2. Press and hold the + and buttons simultaneously for 3 seconds. Release them
and, within 2 seconds, press and hold the + button again for 3 seconds. Then,
P03 displays.
3. Select the required parameter by pressing the + and buttons:
4. Press the + and buttons simultaneously. Te current value of the selected
parameter displays on the screen. Press the + or button to change the value.
5. You can either press the + and buttons simultaneously to confirm the change
or wait for 5 seconds to have the change saved automatically.
6. Repeat steps 3 through 5 to change more parameters.
7. 10 seconds after the last display or setting, all changes are saved and the
thermostat returns to Protection mode.
Reload the factory setting of the control parameters as follows:
1. Set the thermostat to Protection mode .
2. Press the + and buttons simultaneously for 3 seconds. Release them and,
within 2 seconds, press the button twice.
Then 888 displays during the reloading process.
Para-
meter
Meaning Setting range
Factory
setting
P03
Setpoint of heating in
Protection Mode
(Wheat
Stb
)
OFF, 5 °C…Wcool
Stb
8 °C
P04
Setpoint of cooling in
Protection Mode
(Wcool
Stb
)
OFF, Wheat
Stb
…40 °C OFF
P05
Minimum setpoint limitation in
Comfort Mode
(Wmin
Norm
)
5
°C
…Wmax
Norm
5
°C
P06
Maximum setpoint limitation in
Comfort Mode
(Wmax
Norm
f
)
Wmin
Norm
…40
°C
35
°C
P07
Sensor calibration
-
3…
3 K
0 K
P08
Switching differential heating mode SDH
0.5…
4
K
1
K
P09
Switching differential cooling mode SDC
0.5…
4
K
1 K
P14
Dwelling time of auto fan speeds
1…5 min
2 min
P17
Selection of °C or °F
°C or °F
°C
P18 Display of temperature or setpoint
OFF: Setpoint
ON: Room (or return air) temperature
ON
P21 Fan control in Comfort mode
OFF in dead zone
ON in dead zone
ON
P22 Heating/cooling mode
0: Heating only
1: Cooling only
3: Manual H/C changeover
3: Manual
Parameter settings
Parameter reset
Control parameters