User Manual

Table Of Contents
29 / 66
Siemens RDF302 Basic documentation CE1P3079en
Smart Infrastructure 2020-12-01
ON/OFF control
The diagrams below show the control sequence for 2-position.
Heating mode
(automatic changeover
=
heating or heating only)
Cooling mode
(man. /
auto. changeover
=
cooling or cooling only)
Y
½ SDH
1
0
½ SDH
w
3
0
7
6
D
0
6
T[°C]
V1
½ SDH ½ SDH
E1
w
D
Y
½ SDC
1
0
½ SDC
w
3
0
7
6
D
0
5
TC]
V1
½ SDH
½ SDH
E1
x
dz
Heating mode with manual changeover (P01 = 2) (manual changeover = heating)
½ SDH
1
0
½ SDH
w
Y
3
0
7
6
D
0
7
T[°C]
E1
T[°C] Room temperature
W Room temperature setpoint
V1 Control command “Valve” or “Compressor”
E1 Control command “Electric heater”
SDH Switching differential “Heating” (P30)
SDC Switching differential “Cooling” (P31)
X
dz
Dead zone (P33)
w
D
Setpoint differential (P34)
The diagrams only show the PI thermostat’s proportional part.
Setting the sequence and the control outputs
Refer to sections 3.4 "Applications", 3.6.1 "Sequences", and 3.7 "Outputs".
Control sequence
ON/OFF output
Note: