User Manual
Table Of Contents
- 1. About this document
- 2. Summary
- 3. Functions
- 3.1 Temperature control
- 3.2 Operating modes
- 3.3 Room temperature setpoint
- 3.4 Applications overview
- 3.5 Additional functions
- 3.6 Control sequences
- 3.7 Control outputs
- 3.8 Fan control
- 3.9 Multifunctional input, digital input
- 3.10 Handling faults
- 3.11 Modbus RTU mode
- 3.12 Communication objects
- 3.13 Control parameters
- 4. Handling
- 5. Connection
- 6. Mechanical design
- 7. Technical data
22 / 66
Siemens RDF302 Basic documentation CE1P3079en
Smart Infrastructure 2020-12-01
3.4.3 Applications for heat pump systems
*)
Application and output signal, DIP switches, diagram
· 1-stage compressor ON / OFF
(heating or cooling)
1
ON
2 3
· 1-stage compressor with electric
heater
(heating or cooling) ON / OFF
1
ON
2 3
3181S31
N1
T
B1
T
D3
3
1
8
1
S
3
2
N1T
E1
B1
T
D3
· 1-stage compressor ON / OFF
(heating and cooling)
1
ON
2 3
3181S35
N1
T
B1
T
D3
N1 Thermostat
Terminal Y11: Heating or heating / cooling
Terminal Y21: for cooling (H &C)
B1 Return air temperature sensor or external room
temperature sensor (optional)
E1 Electric heater D3 Dewpoint sensor
*)
RDF302.B does not have inputs X1 and X2, so sensor B1 and B2 are not
included in RDF302.B application.