3.3 Room temperature setpoint
3.3.1 Description
The factory setting for the Comfort basic setpoint is 21 °C and can be changed in
the thermostat’s EEPROM via parameter P08 or via Modbus with communication
object "Comfort basic setpoint". The last intervention always wins.
The Comfort setpoint can be adjusted via the +/- buttons,
or via Modbus from a remote device like a touch panel or master unit, etc.
The last intervention always wins.
If the “Temporary setpoint” function is enabled via parameter P69, the Comfort
setpoint adjusted via the + / - buttons or via Modbus is set back to the Comfort
basic setpoint stored in P08 when the operating mode changes.
For energy saving purposes, the setpoint setting range can be limited to minimum
(P09) and maximum (P10).
· If the minimum limit P09 is set lower than the maximum limit P10, both heating
and cooling are adjustable between these 2 limits
· For heating or cooling applications (e.g. 2-stage):
– The setting range in cooling mode is from P09…40 °C in place of 5…40 °C
– The setting range in heating mode is from 5…P10 °C in place of 5…40 °C
· For heating and cooling applications (e.g. 4-pipe):
– The cooling and heating setpoint are adjustable
– The setting range in cooling mode is from P09…40 °C in place of 5…40 °C
– The setting range in heating mode is from 5…P10 °C in place of 5…40 °C
Examples 2-pipe heating OR cooling 4-pipe heating AND cooling
P09 < P10
Cooling setpoint adjustable 18…25 °C
Heating setpoint adjustable 18…25 °C
Cooling setpoint adjustable 18…25 °C
Heating setpoint adjustable 18…25 °C
P09 P10
Cooling setpoint adjustable 25…40 °C
Heating setpoint adjustable 5…21 °C
Use control parameters P11 and P12 to adjust the Economy mode setpoints.
The heating setpoint is factory-set to 15 °C, and the cooling setpoint to 30 °C.
Use control parameters P65 and P66 to adjust the Protection mode setpoints.
The heating setpoint is factory-set to 8 °C (frost protection) and to OFF for cooling.
Comfort mode
Temporary setpoint
Setpoint limitation
P09 < P10
P09 P10
Economy
mode
Protection
m
ode