Technical data

14 / 19
Siemens Web-Server OZW772... V5.2 CE1N5701en
Building Technologies 2014-10-15
Dark No operating voltage DC 24 V
Steady red Web server starts operating system.
Flashing red Web server starts application.
Steady green Web server operational, "Energy indicator" = "Green leaf"
Lit orange Web server operational, "Energy indicator" = "Orange leaf"
Flashing green Web server operational, connected to the portal
green / orange (LED 0.8 s on, 0.2 s off)
Dark No bus power.
Lit KNX operational.
Flashing Communication on KNX.
Dark No function.
Dark No fault (normal operating state).
Lit Acknowledged fault.
Flashing Unacknowledged fault.
Dark KNX addressing mode off.
Lit KNX addressing mode on.
Short (< 2 s) Acknowledges fault message.
Long (> 6 s) Send the system report to the fault e-mail recipient
(not to consumption data, and "Energy indicator" and trend
data recipient).
Short (< 2 s) Press once: KNX addressing mode On
Press again: KNX addressing mode off.
Long (> 6 s) Simultaneously press
and
restores default factory settings.
All configuration data and settings are reset.
The device list, plant diagrams, and unsent
messages are deleted. History data
is not deleted.
Position ON Sending messages is suppressed.
Position OFF
Sending messages permitted.
Switch settings. No function.
1 (red/green/orange)
2 (green)
3 Field bus 2 (reserve)
4 Fault (red)
5 Addressing mode (red)
6 Remote button
7 Addressing mode
9
DIP switch 2