ACS provides standard plant diagrams for RDF KNX thermostats, which depend
on the configuration as follows:
Plant type
Application
Configuration
Application
Configuration
2-pipe
2-pipe fan coil unit
Control sequence: No impact (P01 = any)
Fan operation: Not disabled (P52 <> 0)
Radiator
Control sequence: Heating only (P01 = 0)
Fan operation: Disabled (P52 = 0)
Chilled / heated ceiling
Control sequence: Changeover (P01 = 2,3)
– Fan operation: Disabled (P52 = 0)
Chilled ceiling
Control sequence: Cooling only (P01 = 1)
Fan operation: Disabled (P52 = 0)
2-pipe and
electric
heater
2-pipe fan coil unit with electric heater
Control sequence: No impact (P01 = any)
Fan operation: Not disabled (P52 <> 0)
Single stage with electric heater
Control sequence: No impact (P01 =any)
Fan operation: Disabled (P52 = 0)
4-pipe
4-pipe fan coil unit
Control sequence: Not auto c/o (P01 <> 3)
Fan operation: Not disabled (P52 <> 0)
Chilled ceiling with radiator
Control sequence: No impact (P01 =any)
Fan operation: Disabled (P52 = 0)
Fan coil unit main / secondary
Control sequence: Auto c/o (P01 = 3)
Fan operation: Not disabled (P52 <> 0)
Main / secondary
Control sequence: Auto c/o (P01 = 3)
Fan operation: Disabled (P52 = 0)