Technical data
Table Of Contents
- 1. About this document
- 2. Summary
- 3. Functions
- 3.1 Temperature control
- 3.2 Operating modes
- 3.3 Room temperature setpoints
- 3.4 Applications overview
- 3.5 Additional functions
- 3.6 Control sequences
- 3.7 Control outputs
- 3.8 Fan control
- 3.9 Multifunctional input, digital input
- 3.10 Handling faults
- 3.11 KNX communications
- 3.11.1 S-mode
- 3.11.2 LTE mode
- 3.11.3 Zone addressing in LTE mode (in conjunction with Synco)
- 3.11.4 Example of heating and cooling demand zone
- 3.11.5 Send heartbeat and receive timeout
- 3.11.6 Startup
- 3.11.7 Heating and cooling demand
- 3.11.8 Fault function on KNX
- 3.11.9 KNX switching groups (RDF301.50, RDF301.50H only)
- 3.12 Communication objects (S-mode)
- 3.13 Communication objects (LTE-mode)
- 3.14 Control parameters
- 4. Handling
- 5. Supported KNX tools
- 6. Connection
- 7. Mechanical design
- 8. Technical data

Parameter
Name
Factory setting
Range
RDF301..
RDF600KN
Dependen-
cies
Expert level
P52
Fan control
1
0 = Disabled
1 = Enabled
2 = Heating only
3 = Cooling only
P53
Fan speeds
3-speed
1 = 1-speed
2 = 3-speed
P52
P54
Fan overrun time
60 sec
0...360 sec
P52, Appl.
P55
Fan speed switching point
high
100%
80...100%
P52, P53,
DIP
P56
Fan speed switching point
med
65%
30..75%
P52, P53,
DIP
P57
Fan speed switching point
low
10% 1...15%
P52, P53,
DIP
P58 Fan start kick ON
ON: Enabled
OFF: Disabled
P52
P59
On time minimum fan
2 min
1...6 min
P52
P60
Periodic fan kick Comfort
RDF301...
RDF600KN
0
OFF
0…89 min, OFF(90)
x
x
P52
P61
Periodic fan kick Eco
OFF
0…359 min, OFF(360)
P52
P62
Service filter
OFF (0)
OFF, 100…9900 h
P52
P65
Protection heating
setpoint
8 °C
OFF, 5…WCoolProt;
WCoolProt = 40 °C max
P66 Protection cooling setpoint OFF
OFF, WHeatProt… 40;
WHeatProt = 5°C min
P67
Fan start delay
(RDF600KN )
4)
0 s
0...360 s
x
P52, P46
P68
Temporary Comfort mode
0 (= OFF)
0...360 min
P02
P69
Temporary Comfort
setpoint
OFF
OFF = Disabled
ON = Enabled
P71
Restore factory setting
OFF
OFF = Disabled
ON = Reload start
"8888" is displayed for 3s during
reload process
4) Not available on RDF600KN SW < V1.8
5) On RDF600KN SW < V1.8, setting range 0…8
Parameter
Name
Factory setting
Range
RDF301..
RDF600KN
Dependen-
cies
Communications
P81
Device address
1)
255
1…255
P82
Geographical zone
(apartment)
2)
---
---, 1...126
P83
Geographical zone (room)
2)
1 ---, 1...63
P84
Heat distr zone heating
coil
--- ---, 1...31
Appl., P01
P85
Refrig distr zone cooling
coil
---
---, 1...31
Appl., P01
P88
Transformation
Precomfort
0
0 = Economy
1 = Comfort
1) Physical address = Area.Line. DeviceAddress. Factory setting for Area = 0, Line = 2.
Can be changed by special management service e.g. from line coupler or via ACS commissioning tool.
2) Type = geographical zone A.R.S. In RDF sub zone = fixed value 1.
69 / 92
Siemens RDF301, RDF301.50..., RDF600KN Basic documentation CE1P3171en
Building Technologies Functions 2014-05-23