Technical data

Table Of Contents
3.14.3 Parameters of the "Service level"
Parameter
Name
Factory setting
Range
RDF301..
RDF600KN
Dependencies
Service level
P01
Control sequence
2-pipe:
1 = Cooling only
4-pipe:
4 = Heating and Cooling
0 = Heating only
1 = Cooling only
2 = H/C changeover manual
3 = H/C changeover auto
4 = Heating and Cooling
P02
Operation via room op
selector
1 1 = Auto Protection
2 = Auto - Comfort - Economy
Protection
P01
P04
Unit
C (0)
C = ° Celsius
F = ° Fahrenheit
P05
Measured value correction
0 K
3 ... 3 K
P06 Standard display 0
0 = Room temperature
1 = Setpoint
P07
Additional display
information
0
0 = --- (No display)
1 = °C and °F
2 = Outside temperature (via bus)
3 = Time of day (12h) (via bus)
4 = Time of day (24h) (via bus)
P08
Comfort basic setpoint
21 °C
5 ... 40 °C
P09 Comfort setpoint minimum 5 °C 5 ... 40 °C
P10
Comfort setpoint maximum
35 °C
5 ... 40 °C
P11
Economy heating setpoint
15 °C
OFF, 5 ... WCoolEco;
WCoolEco = 40 °C max
P12
Economy cooling setpoint
30 °C
OFF, WHeatEco ... 40 °C;
WHeatEco = 5C min
P13
Electric heater when
cooling
ON
ON: Enabled
OFF: Disabled
Appl.
P14 Button lock 0
0 = Unlocked
1 = Auto lock
2 = Manual lock
P15
Fan stage in dead zone
(Comfort)
(RDF600KN)
4)
0
0 = Disabled
1 = Low speed (Heat and Cool)
2 = Low speed (Cooling only)
x
4) Not available on RDF600KN SW < V1.8
Parameter display depends on selected application and function.
Note:
67 / 92
Siemens RDF301, RDF301.50..., RDF600KN Basic documentation CE1P3171en
Building Technologies Functions 2014-05-23