Technical data
Table Of Contents
- 1. About this document
- 2. Summary
- 3. Functions
- 3.1 Temperature control
- 3.2 Operating modes
- 3.3 Room temperature setpoints
- 3.4 Applications overview
- 3.5 Additional functions
- 3.6 Control sequences
- 3.7 Control outputs
- 3.8 Fan control
- 3.9 Multifunctional input, digital input
- 3.10 Handling faults
- 3.11 KNX communications
- 3.11.1 S-mode
- 3.11.2 LTE mode
- 3.11.3 Zone addressing in LTE mode (in conjunction with Synco)
- 3.11.4 Example of heating and cooling demand zone
- 3.11.5 Send heartbeat and receive timeout
- 3.11.6 Startup
- 3.11.7 Heating and cooling demand
- 3.11.8 Fault function on KNX
- 3.11.9 KNX switching groups (RDF301.50, RDF301.50H only)
- 3.12 Communication objects (S-mode)
- 3.13 Communication objects (LTE-mode)
- 3.14 Control parameters
- 4. Handling
- 5. Supported KNX tools
- 6. Connection
- 7. Mechanical design
- 8. Technical data

3.14 Control parameters
A number of control parameters can be readjusted to optimize control performance.
This can be done on the thermostat via HMI or via commissioning / operating tool.
These parameters can also be set during operation without opening the unit.
In the event of a power failure, all control parameter settings are retained, see page 51.
The control parameters are assigned to 2 levels:
• "Service level", and
• "Expert level" including communications, diagnostics and test.
The "Service level" contains a small set of parameters to set up the thermostat for
the HVAC system and to adjust the user interface. These parameters can be
adjusted any time.
Change parameters at the "Expert level" carefully, as they impact the thermostat’s
control performance and functionality.
3.14.1 Parameter setting via local HMI
1. Press buttons + and – simultaneously for 4 seconds.
Release and press button + again within 2 seconds until the display shows "P01".
Continue with step 2.
1. Press buttons + and – simultaneously for 4 seconds.
Release and press button – again within 2 seconds until the display shows "P01".
2. Repeatedly press the + or – button to select the required parameter.
P01 P02 P08 P14
+- +
- -
+
3171z99
End
-
+
-
P13
+-
3. Press + and – simultaneously. The current value of the selected parameter
begins to flash, allowing you to change the value by repeatedly pressing + or –.
4. The next parameter is displayed when you press + and – again simultaneously.
5. Repeat steps 2 to 4 to display and change additional parameters.
6. Press + or – until "End" is displayed, and then press + and – simultaneously to
save the change and exit parameter entry mode.
The factory setting for the control parameters can be reloaded via parameter P71,
by changing the value to "ON", and confirming by pressing buttons + and –
simultaneously. The display shows "8888" during reload.
Enter only "Service"
level
Enter "Service" and
"
Expert" level.
Adjust parameters
Reset parameters
65 / 92
Siemens RDF301, RDF301.50..., RDF600KN Basic documentation CE1P3171en
Building Technologies Functions 2014-05-23