Technical data
Table Of Contents
- 1. About this document
- 2. Summary
- 3. Functions
- 3.1 Temperature control
- 3.2 Operating modes
- 3.3 Room temperature setpoints
- 3.4 Applications overview
- 3.5 Additional functions
- 3.6 Control sequences
- 3.7 Control outputs
- 3.8 Fan control
- 3.9 Multifunctional input, digital input
- 3.10 Handling faults
- 3.11 KNX communications
- 3.11.1 S-mode
- 3.11.2 LTE mode
- 3.11.3 Zone addressing in LTE mode (in conjunction with Synco)
- 3.11.4 Example of heating and cooling demand zone
- 3.11.5 Send heartbeat and receive timeout
- 3.11.6 Startup
- 3.11.7 Heating and cooling demand
- 3.11.8 Fault function on KNX
- 3.11.9 KNX switching groups (RDF301.50, RDF301.50H only)
- 3.12 Communication objects (S-mode)
- 3.13 Communication objects (LTE-mode)
- 3.14 Control parameters
- 4. Handling
- 5. Supported KNX tools
- 6. Connection
- 7. Mechanical design
- 8. Technical data

Obj
Object name
Function
Type/ length
Flags
An electric heater can be disabled with this communication object
(e.g. to meet tariff regulations).
The same function is also available via local multifunctional input
X1/X2 (parameter P38, P40).
Only one input source must be used, either local input X1/X2 or
KNX bus.
30
Heating / cooling
changeover
Heat /
Cool
1.100
1 bit
CWU
Changeover information transmitted via bus.
Default: Current mode before power down.
The same function is also available via local multifunctional input
X1/X2 (parameter P38, P40).
Only one input source must be used, either local input X1/X2 or
KNX bus..
31
Application mode
HVAC
control
mode
20.105
8 bit
CWU
0
Auto (default)
Heating and/or cooling
1
Heat
Heating only
2
Morning warmup*
Heating only
3
Cool
Cooling only
5
Precool*
Cooling only
6
OFF
Neither heating nor cooling
8
Emergency heat*
Heating only
9
Fan only
Fan runs at high speed
* Function handled like Heat (1) or Cool (3)
32
Enable fan
command value
Enable
Disable
1.003
1 bit
CWU
Set fan mode to Auto (disable) or Manual (enable) by a KNX
control unit. If Manual, the value received on Fan command value
(34) will be used to command the fan speed.
Default: Enable
The last interaction wins – either from the local fan mode button or
via bus.
33
Fan operation
Auto
Manual
1.001
1 bit
CRT
Indicates the status of the fan mode: Auto (0) or Manual (1).
34
Fan command
value
0…100%
5.001
8 bit
CWU
The fan can be set to a specified speed by a KNX control unit
when manual fan operation is enabled.
Speed
Fan command value (physical KNX value)
1
1...33% (1…85)
2
34…67% (86...170)
3
68…100% (171…255)
Fan speed "0" is not supported by the thermostat and the fan
speed will remain unchanged.
35
Fan output
0…100%
5.001
8 bit
CRT
Indicates the current fan speed as a value 0...100%
Speed
Fan output (physical KNX value)
OFF
0% (0)
1
33% (84 )
2
66% (186)
3
100% (255)
36
37
38
Fan speed 1
Fan speed 2
Fan speed 3
ON
OFF
1.001
1 bit
CRT
Indicate the state of the relay outputs
39
40
X1: Temperature
X2: Temperature
Temp.
value
9.001
2 Byte
CRT
Indicate the values of the temperature sensors connected to the
local inputs X1 / X2
41
42
X1: Digital
X2: Digital
ON
OFF
1.001
1 bit
CRT
Obj
Object name
Function
Type/ length
Flags
Indicate the status of the digital inputs (adjusted by parameters
P39/P41) including considering of operating action
44
Outside
temperature
Temp.
value
9.001
2 Byte
CWU
The outside temperature measured by a KNX sensor can be
displayed on the thermostat, if parameter P07 "Additional user
information" is set = 2 (outside temperature).
45
Buttons left
ON/OFF
ON
OFF
1.001
1 bit
CT
51
Buttons right
ON/OFF
Switch control: Parameter ON/OFF functions = Top: ON; Bottom:
OFF
When pressing the button, the corresponding switching telegram is
sent immediately.
45
Button
top left: ON/OFF
ON
OFF
1.001
1 bit
CT
CWTU 1)
46
Button
bottom left: ON/OFF
51
Button
top right: ON/OFF
52
Button
bottom: Right
ON/OFF
Switch control: Parameter ON/OFF functions = 2 "ON/OFF"
functions.
When pressing the button, the corresponding switching telegram is
sent immediately: ON, OFF or Toggle.
1) If "Toggle" is selected, the communication object becomes
output and synchronization input
45
51
Buttons left:
ON/OFF
Buttons right:
ON/OFF
ON
OFF
1.001
1 bit
CT
47
53
Buttons left: Dim
up/down
Buttons right:
Dim up/down
Darker /
Brighter
1.001
4 bit
CT
On a short operation of the button, a switching telegram is sent,
e.g. press left top button: "On" is sent, press left bottom button:
"OFF" is sent.
When pressing the buttons longer, a dimming telegram is sent,
e.g. press left top button: "Brighter" is sent, press left bottom
button: "Darker" is sent.
On releasing the button, a "Stop" telegram is sent.
48
54
Buttons left:
Blind step/stop
Buttons right:
Blind step/stop
Step /
Stop
1.001
1 bit
CT
49
55
Buttons left:
Blind up/down
Buttons right:
Blind up/down
Up /
Down
1.001
1 bit
CT
On a short operation of the button, a telegram is sent to adjust the
louvers or stop the blinds if moving up or down.
On a long operation of the button, a telegram is sent to raise or
lower the blinds (up or down)
50
56
Buttons left:
Scene
Buttons right:
Scene
Scene
control
18.001
8 bit
CT
62 / 92
Siemens RDF301, RDF301.50..., RDF600KN Basic documentation CE1P3171en
Building Technologies Functions 2014-05-23