Technical data
Table Of Contents
- 1. About this document
- 2. Summary
- 3. Functions
- 3.1 Temperature control
- 3.2 Operating modes
- 3.3 Room temperature setpoints
- 3.4 Applications overview
- 3.5 Additional functions
- 3.6 Control sequences
- 3.7 Control outputs
- 3.8 Fan control
- 3.9 Multifunctional input, digital input
- 3.10 Handling faults
- 3.11 KNX communications
- 3.11.1 S-mode
- 3.11.2 LTE mode
- 3.11.3 Zone addressing in LTE mode (in conjunction with Synco)
- 3.11.4 Example of heating and cooling demand zone
- 3.11.5 Send heartbeat and receive timeout
- 3.11.6 Startup
- 3.11.7 Heating and cooling demand
- 3.11.8 Fault function on KNX
- 3.11.9 KNX switching groups (RDF301.50, RDF301.50H only)
- 3.12 Communication objects (S-mode)
- 3.13 Communication objects (LTE-mode)
- 3.14 Control parameters
- 4. Handling
- 5. Supported KNX tools
- 6. Connection
- 7. Mechanical design
- 8. Technical data

• For a detailed description of KNX (topology, bus supply, function and setting of
LTE zones, filter tables, etc.), see "Communication via the KNX bus for Synco
700, 900 and RXB/RXL, Basic Documentation" [6].
• LTE mode data points and settings are described in the Synco Application
Manual [12].
• To engineer and commission a specific system, use the Synco700 planning and
commissioning protocol (XLS table in HIT, [7]).
3.11.3 Zone addressing in LTE
mode (in conjunction with
Synco)
In cases where RDF KNX room thermostats are used in LTE mode (e.g. in
conjunction with Synco), zone addresses need to be allocated.
The following zone address must be defined together with the Synco devices at the
planning stage depending on the application.
Short description
Factory setting
Parameter
Geographical zone (apartment)
--- (out of service)
P82
Geographical zone (room)
1
P83
Heat distr zone heating coil
1
P84
Refr distr zone cooling coil
1
P85
"Subzone" of "Geographical zone" is fix 1 (not adjustable).
The device will send and receive LTE communication signals only if the zone
address is valid (not OSV = out of service).
Engineering and
commissioning
Note:
53 / 92
Siemens RDF301, RDF301.50..., RDF600KN Basic documentation CE1P3171en
Building Technologies Functions 2014-05-23