To let the heating / cooling coil reach its temperature, the fan start can be delayed
by a time period set via parameter P67.
Y
0
T
P67
1
31
81D23
Q
T
This function (via parameter P67) is not implemented into RDF600KN SW version
< V1.8.
Fa
n start delay
(
RDF600KN)
Note:
48 / 92
Siemens RDF301, RDF301.50..., RDF600KN Basic documentation CE1P3171en
Building Technologies Functions 2014-05-23