Technical data
Table Of Contents
- 1. About this document
- 2. Summary
- 3. Functions
- 3.1 Temperature control
- 3.2 Operating modes
- 3.3 Room temperature setpoints
- 3.4 Applications overview
- 3.5 Additional functions
- 3.6 Control sequences
- 3.7 Control outputs
- 3.8 Fan control
- 3.9 Multifunctional input, digital input
- 3.10 Handling faults
- 3.11 KNX communications
- 3.11.1 S-mode
- 3.11.2 LTE mode
- 3.11.3 Zone addressing in LTE mode (in conjunction with Synco)
- 3.11.4 Example of heating and cooling demand zone
- 3.11.5 Send heartbeat and receive timeout
- 3.11.6 Startup
- 3.11.7 Heating and cooling demand
- 3.11.8 Fault function on KNX
- 3.11.9 KNX switching groups (RDF301.50, RDF301.50H only)
- 3.12 Communication objects (S-mode)
- 3.13 Communication objects (LTE-mode)
- 3.14 Control parameters
- 4. Handling
- 5. Supported KNX tools
- 6. Connection
- 7. Mechanical design
- 8. Technical data

On 4-pipe applications, the Comfort setpoint (w) is in the middle of the dead zone,
between the heating and cooling sequence.
The dead zone can be adjusted via parameter P33.
If manual changeover is selected, then either the cooling sequence or the heating
sequence is released. In this case, the Comfort setpoint is at the selected heating
or cooling sequence.
Comfort mode
Economy /
Protection mode
Application
Heating and cooling Heating only
1)
Cooling only
1)
Heating and/or
cooling
4-pipe
1) Manual changeover, P01 = 2
W = setpoint in Comfort mode
W
HeatEco/Prot
= heating setpoint for Economy or Protection mode
W
CoolEco/Prot
= cooling setpoint for Economy or Protection mode
YE = electric heater sequence
4-pipe applications
Y
T
W
HeatEco/Prot
W
CoolEco/Prot
Y
T
W
Y
T
W
Y
T
W
42 / 92
Siemens RDF301, RDF301.50..., RDF600KN Basic documentation CE1P3171en
Building Technologies Functions 2014-05-23