Technical data
Table Of Contents
- 1. About this document
- 2. Summary
- 3. Functions
- 3.1 Temperature control
- 3.2 Operating modes
- 3.3 Room temperature setpoints
- 3.4 Applications overview
- 3.5 Additional functions
- 3.6 Control sequences
- 3.7 Control outputs
- 3.8 Fan control
- 3.9 Multifunctional input, digital input
- 3.10 Handling faults
- 3.11 KNX communications
- 3.11.1 S-mode
- 3.11.2 LTE mode
- 3.11.3 Zone addressing in LTE mode (in conjunction with Synco)
- 3.11.4 Example of heating and cooling demand zone
- 3.11.5 Send heartbeat and receive timeout
- 3.11.6 Startup
- 3.11.7 Heating and cooling demand
- 3.11.8 Fault function on KNX
- 3.11.9 KNX switching groups (RDF301.50, RDF301.50H only)
- 3.12 Communication objects (S-mode)
- 3.13 Communication objects (LTE-mode)
- 3.14 Control parameters
- 4. Handling
- 5. Supported KNX tools
- 6. Connection
- 7. Mechanical design
- 8. Technical data

3.6.8 Setpoints and sequences
On changeover applications, the Comfort setpoints for heating and cooling
sequence are the same (w).
On 2-pipe applications with electric heater, the Comfort setpoint is either at the first
heating sequence (in heating mode) or at the cooling sequence (in cooling mode).
The setpoints for Economy and Protection mode are below the Comfort setpoints
(heating) and above the Comfort setpoints (cooling).
They can be set via parameters P11, P12 (Economy mode) and P65, P66
(Protection mode).
w
3181D127
T[°C]
w
HeatProt
w
CoolProt
w
HeatEco
w
CoolEco
Comfort mode
Economy / Protection mode
Application
Heating
Cooling
Heating Cooling
2-pipe
2-pipe and
electric
heater
1) If P13 = ON
2) In case of manual changeover (P01 = 2), the first heating sequence is disabled to prevent heating
(electric heater) and cooling (coil) at the same time
W = setpoint in Comfort mode
W
HeatEco/Prot
= setpoint heating in Economy or Protection mode
W
CoolEco/Prot
= setpoint cooling in Economy or Protection mode
YR = radiator sequence
YE = electric heater sequence
2-pipe applications
Y
T
W
HeatEco/Prot
W
CoolEco/Prot
YE
1)
Y
T
W
HeatEco/Prot
YE
2)
Y
T
W
YE
1)
Y
T
W
YE
2)
Y
T
W
CoolEco/Prot
Y
T
W
HeatEco/Prot
Y
T
W
Y
T
W
41 / 92
Siemens RDF301, RDF301.50..., RDF600KN Basic documentation CE1P3171en
Building Technologies Functions 2014-05-23