Technical data

Table Of Contents
3.6.7 Compressor applications
For compressor applications,
set the corresponding basic application
disable the fan (P52) or set the fan speed (P53)
The following applications are available:
Application for compressor
Set basic application
See
section
Sequences
1-stage compressor
for heating or cooling
2-pipe 3.6.3
H ( \ )
C ( / )
1-stage compressor and electric
heater
(for cooling only: disable
electric heater via P13)
2-pipe and electric heater 3.6.4
El H + H ( \ \ )
El H + C (
\ / )
C ( / )
1-stage compressor
for heating and cooling
4-pipe 3.6.5
H + C ( \ / )
Minimum ON/OFF time: P48 / P49
Fan operation:P52 (0 = disabled, 1 = enabled)
Fan speed: P53 (1 = 1-speed, 2 = 3-speed)
Note:
40 / 92
Siemens RDF301, RDF301.50..., RDF600KN Basic documentation CE1P3171en
Building Technologies Functions 2014-05-23