Technical data

Table Of Contents
The diagrams below show the control sequence for 2-position control.
Heating mode with manual selection
(P01 = 2)
Cooling mode with manual selection
(P01 = 2)
Y
½ SDC
1
0
½ SDC
w
3076D13
T[°C]
Y2
Heating and cooling mode (P01 = 04)
Y
½ SDC
1
0
½ SDC
w
3076D11
T[°C]
Y2
½ SDH ½ SDH
Y1
½
x
dz
½
x
dz
T[°C] Room temperature
w Room temperature setpoint
Y1 Control command "Valve" or "Comp." (H)
Y2 Control command "Valve" or "Comp." (C)
SDH Switching differential "Heating" (P30)
SDC Switching differential "Cooling" (P31)
X
dz
Dead zone (P33)
The diagrams only show the PI thermostat’s proportional part.
For the fan sequence see section 3.8.
Setting the sequence and the control outputs
Refer to sections 3.4 "Applications", 3.6.1 "Sequences", and 3.7 "Outputs".
3.6.6 Chilled / heated ceiling and radiator applications
For chilled / heated ceiling and radiator,
set the corresponding basic application
disable the fan (P52)
The following applications are available:
Application for
chilled / heated ceiling, radiator
Set basic application
See
section
Sequences
Chilled / heated ceiling with
changeover
2-pipe 3.6.3
H ( \ )
C ( / )
Chilled / heated ceiling & el heater
(cooling only: disable el heater
via P13)
2-pipe and electric heater 3.6.4
El H + H ( \ \ )
El H + C (
\ / )
C ( / )
Chilled ceiling and radiator
4-pipe 3.6.5
H + C ( \ / )
½ SDH
1
0
½ SDH
w
Y
3076D01
T[°C]
Y1
ON/OFF control
Note: