Technical data
Table Of Contents
- 1. About this document
- 2. Summary
- 3. Functions
- 3.1 Temperature control
- 3.2 Operating modes
- 3.3 Room temperature setpoints
- 3.4 Applications overview
- 3.5 Additional functions
- 3.6 Control sequences
- 3.7 Control outputs
- 3.8 Fan control
- 3.9 Multifunctional input, digital input
- 3.10 Handling faults
- 3.11 KNX communications
- 3.11.1 S-mode
- 3.11.2 LTE mode
- 3.11.3 Zone addressing in LTE mode (in conjunction with Synco)
- 3.11.4 Example of heating and cooling demand zone
- 3.11.5 Send heartbeat and receive timeout
- 3.11.6 Startup
- 3.11.7 Heating and cooling demand
- 3.11.8 Fault function on KNX
- 3.11.9 KNX switching groups (RDF301.50, RDF301.50H only)
- 3.12 Communication objects (S-mode)
- 3.13 Communication objects (LTE-mode)
- 3.14 Control parameters
- 4. Handling
- 5. Supported KNX tools
- 6. Connection
- 7. Mechanical design
- 8. Technical data

3.6 Control sequences
3.6.1 Sequences overview (setting via parameter P01)
The main control sequence (i.e. the water coil sequence of the fan coil unit) can be
set via parameter P01.
The following sequences can be activated in the thermostats (each without or with
auxiliary heating).
The available sequences depend on the application (selected via DIP switch, see
section 3.4).
Parameter
P01 = 0
P01 = 1
P01 = 2
P01 = 3
P01 = 4
Sequence
T °C
T °C
T °C
T
T °C
Available
for basic
application
1)
:
Heating Cooling
*) 2-pipe with
el. heater
Manually select
heating or
cooling
sequence
Automatic
heating /
cooling
changeover via
external water
temperature
sensor or
remote switch
Heating and
cooling
sequence, i.e.
4-pipe
2-pipe,
2-pipe & el heater
4-pipe
2)
2)
1) For chilled / heated ceiling and radiator applications, see section 3.6.6;
for compressor applications, see section 3.6.7.
2) For manual and automatic changeover with 4-pipe applications,
see section 3.6.5:
– 4-pipe manual changeover (P01 = 2) means activating either cooling or
heating outputs.
– 4-pipe automatic changeover (P01 = 3) means swapping the control outputs
according to a heating / cooling sensor or remote switch
("main and secondary" application), see section 3.6.5.
For the relation between setpoints and sequences, see section 3.6.8.
Note:
32 / 92
Siemens RDF301, RDF301.50..., RDF600KN Basic documentation CE1P3171en
Building Technologies Functions 2014-05-23