Technical data
Table Of Contents
- 1. About this document
- 2. Summary
- 3. Functions
- 3.1 Temperature control
- 3.2 Operating modes
- 3.3 Room temperature setpoints
- 3.4 Applications overview
- 3.5 Additional functions
- 3.6 Control sequences
- 3.7 Control outputs
- 3.8 Fan control
- 3.9 Multifunctional input, digital input
- 3.10 Handling faults
- 3.11 KNX communications
- 3.11.1 S-mode
- 3.11.2 LTE mode
- 3.11.3 Zone addressing in LTE mode (in conjunction with Synco)
- 3.11.4 Example of heating and cooling demand zone
- 3.11.5 Send heartbeat and receive timeout
- 3.11.6 Startup
- 3.11.7 Heating and cooling demand
- 3.11.8 Fault function on KNX
- 3.11.9 KNX switching groups (RDF301.50, RDF301.50H only)
- 3.12 Communication objects (S-mode)
- 3.13 Communication objects (LTE-mode)
- 3.14 Control parameters
- 4. Handling
- 5. Supported KNX tools
- 6. Connection
- 7. Mechanical design
- 8. Technical data

Operating mode switchover
In room 1, the window is opened briefly, once in the morning, once in late
afternoon and once at night (1). Only the opening in the morning has a direct
impact on the effective room operating mode.
During lunch break, the time schedule changes to Precomfort. The mode remains
in Comfort as set by parameter "Transformation Precomfort" (P88 = 1).
Time schedule
Window contact
Room 1
Effective room
operating mode
Room 1
Comfort
Precomfort
Economy
Protection
Window open
Window closed
Comfort
Economy
Protection
08:00
17:0013:0012:00
1)
06:00
20:00
1)
1)
2)
3171Z91
Example 1 (RDF301…)
19 / 92
Siemens RDF301, RDF301.50..., RDF600KN Basic documentation CE1P3171en
Building Technologies Functions 2014-05-23