Datasheet
4
Room automation
Overview and selection tools
Product range overview
Siemens Switzerland Ltd http://www.siemens.com/buildingtechnologies-productcatalog 2014
Building Technologies Division
4-6
PCX3 Room automation stations overview
PXC3.E72 PXC3.E72A PXC3.E75 PXC3.E75A
Max. numbers of rooms / room segments 4 / 8 4 / 8 8 / 16 8 / 16
System communication BACnet / IP BACnet / IP BACnet / IP BACnet / IP
HMI Automation level
Desigo Touch and Web and PX Web
PXM20
PXM10
QAX
QMX
■■■■
Web based test and setuptool
■■■■
System functions (BACnet)
Alarms
■* ■* ■* ■*
Time schedules
■* ■* ■* ■*
Trend
■■■■
Programming
■■■■
Peripheral bus
Bus for I/O module
■■■■
KNX PL-Link
1)
/ KNX S-Mode
■■■■
DALI
■■
Number of Input/Output for TX I/O Modulen 72 72 200 200
* In combination with PX System controller PXC00-E.D only
1)
Dedicated devices with KNX PL-Link
Overview I/O module TXM1..
Product TXM1.8D TXM1.16D TXM1.8U TXM1.6R TXM1.6RL TXM1.8RB TXM1.8T
Number of Input/Output 8 16 8 6 6 8 8
Functionality
Local operation
LC-Display
3-colored I/O status LED
■
Green colored I/O status LED
■■■■■■
Digital inputs (DI)
Message signal (open/closer)
■■■
Message impulse
■■■
Counter 25 Hz (Bouncer free)
■
1)
■
Analog inputs (AI)
LG-Ni1000
■
Pt1000 / 0...2500 Ohm
■
T1
■
DC 0...10V
■
Analog outputs (AO)
DC 0...10V
■
Digital outputs (DO)
Continuous contact on/off
■■
Continuous contact 3-stage
■
3-point output (stroke model)
■■
Impulse on/off
■
Impulse
■
Impulse 3-stage
■
Bistable contact
■
Contact for control of blinds
■
Modulating (PWM)
■
All I/O points of a module are confi gurable on any, implemented functionality. The module TX1.OPEN enables the integration of Modbus, M-bus etc.
via RS232, 485 on the PXC50/100/200..D.