Datasheet
Automation controls
Automation stations
Integral migration PXC-NRU..
3-15
2014Some products are not available in every country
www.siemens.com/buildingtechnologies-productcatalog
Siemens Switzerland Ltd
Building Technologies Division
3
Data sheet N9761
Operating voltage AC 24 V
Frequency 50/60 Hz
Power consumption 18 VA
Communication Bus: TX-I/O island bus to TXB1.PBUS
Universal inputs‚ number 16
Universal outputs‚ number 16
Digital inputs‚ number 8
Digital outputs‚ number 8
Stock No. Product No.
BPZ:PXC-NRUD PXC-NRUD
Data sheet N9760
Operating voltage AC 24 V
Frequency 50/60 Hz
Power consumption 26 VA
Communication Bus: BACnet / LonTalk
Bus: BACnet / PTP (point to point)
Room unit: PPS2
Dimensions (W x H x D) 265 x 295 x 100 mm
Universal inputs‚ number 16
Universal outputs‚ number 8
Digital inputs‚ number 24
Digital outputs‚ number 16
Adapter plug-in circuit board for INTEGRAL NK modules‚ intgrates 48 data
points in Desigo
Stock No. Product No.
BPZ:PXC-NRUF PXC-NRUF
This adapter‚ combined with an automation station PXC100..D‚ serves as a replacement for the modular
automation stations NRUA/A‚ NRUB/A‚ NRUC/A and NRUD/A.
Fixed data point mix for 48 physical data points per adapter DI=8‚ DO=8‚ UI/UO=32.
Automation station for INTEGRAL migration‚ intgrates 64 data points in Desigo
The adapter consists of a plug-in circuit board with front plate.
It is inserted into an existing card housing NHGB.
In existing INTEGRAL plants‚ you can replace compact automation units NRUE/A‚ NRUF/A and NRUT/A
with the PXC NRUF automation station.
Fixed data point mix for 64 physical data points per automation station UI=16‚ DI=24‚ DO=16‚ UO=8.
V BTL tested BACnet communication on LonTalk or PTP acoording to BACnet standard (rev 1.10) include
B-BC profile
V AMEV profiles AS-A and AS-B according to guide line 'BACnet 2011 - Version 1.1'
PXC-NRUD
PXC-NRUF