Datasheet
Automation controls
Automation stations
Desigo™ PX Open
3-11
2014Some products are not available in every country
www.siemens.com/buildingtechnologies-productcatalog
Siemens Switzerland Ltd
Building Technologies Division
3
Product Title Data sheet Stock No. Product No.
PX KNX S-mode card N9280 BPZ:PXA30-K11 PXA30-K11
Card for PX KNX automation station
System controller for the integration N9221 BPZ:PXC00-U PXC00-U
Hardware for PX KNX
Stock No. Product No.
BPZ:PX KNX PX KNX
Stock No. Product No.
BPZ:PX M-Bus PX M-Bus
PX KNX system controller
PX M-bus system controller
Integration of room controllers from the Desigo RXB and Desigo RXL product range and from KNX third-
party systems into the Desigo building automation and control system (interface functionality). Further
functions: Grouping of rooms and performance of higher level system functions.
V BTL tested BACnet communication on LonTalk or IP acoording to BACnet standard (rev 1.10) include
B-BC profile
V AMEV profiles AS-A and AS-B according to guide line 'BACnet 2011 - Version 1.1'
Functions
KNX data points are mapped to BACnet data points and vice versa. The PX KNX system controller per-
forms the following major tasks:
V Compression of Desigo RXB/RXL room controller data and other KNX data points (e.g. room thermo-
stats RDG/ RDF/ RDU) at the automation level
V Mapping of Desigo RXB/RXL and other KNX applications to BACnet for monitoring and operation pur-
poses (grouped according to function:HVAC‚ lighting and blinds)
V Performance of higher level functions for room automation: Room and supply-related groups‚ system
functions such as changeover‚ summer/winter compensation‚ etc.
The RXB/RXL and KNX applications are mapped to the PX KNX system controller so that a room view is
created. This allows for the grouping of rooms‚ e.g. for shared occupancy schedules‚ lighting or blind
commands‚ etc
Hardware
Modular system controller PXC00-U with PXA30-K11 card.
V Without expansion module in the left slot the communication mode BACnet/LonTalk is activated.
V With the expansion module PXA30-N in the left slot the communication mode BACnet/IP is active.
M-bus datapoints are mapped to BACnet datapoints and vice-versa. The PX M-bus system controller per-
forms the following major tasks.
V BTL tested BACnet communication on LonTalk or IP acoording to BACnet standard (rev 1.10) include
B-BC profile
V AMEV profiles AS-A and AS-B according to guide line 'BACnet 2011 - Version 1.1'
Functions
V Acquisition of consumption data and remote monitoring of max. 250 consumption meters and heat
meters
V Compression of consumption and heat meter data volume at the automation level
V Mapping of M-bus data to BACnet
V Trend objects for meter monitoring
Hardware
Modular system controller PXC00-U with PXA30-RS.. card.
V Without expansion module in the left slot the communication mode BACnet/LonTalk is activated.
V With the expansion module PXA30-N in the left slot the communication mode BACnet/IP is active.
PX KNX
PX M-Bus