Datasheet
3
Automation functions
Overview and selection tools
Overview of product details
Siemens Switzerland Ltd http://www.siemens.com/buildingtechnologies-productcatalog 2014
Building Technologies Division
3-4
Functions of PXA40... / PXA30... for the modular PX automation stations and system controllers
Modular
PXC...D
Modular
PXC...-E.D
System Controller
PXC00-U
Functions PXA40-T PXA40-W0 PXA40-W1 PXA40-W2 PXA30-N
Ethernet interface RJ45
■
Modem connection
■■■■
BACnet on Ethernet / IP
■
Generic PX Web
(ethernet or PPP)
■
1)
■■
Graphic PX Web
(ethernet or PPP)
■
1)
■
Remote management
BACnet (PTP)
■
2)
■
2)
■
2)
■
2)
Remote management
PX Web (PPP)
■
2)
■
2)
■
2)
Deliver alarms via SMS
over RS232
■
2)
■
2)
■
2)
Deliver alarms via e-mail
over ethernet
■■■
1)
For the connected automation station / system controller only
2)
The modern connection can be configured as follows:
- either for Remote management (PTP)
- or for remote management PX Web generic / graphic and Alarming via SMS
Overview TX-I/O™ module
range TXM1..
Type TXM1.8D TXM1.16D TXM1.8U TXM1.8U-ML TXM1.8X TXM1.8X-ML TXM1.6R TXM1.6R-M TXM1.8P TXM1.6RL TXM1.8T
Number of I/Os 8 16 8 8 8 8 6 6 8 6 8
Functionality
Local operation
■■
■
LC-Display
■■
3-colored I/O status LED
■ ■
Green colored I/O status LED
■■ ■ ■ ■ ■ ■■■
Digital inputs (DI)
Message signal (open/closer)
■■■■■ ■
Message impulse
■■■■■ ■
Counter 10 Hz (with debouncing)
■
1-8
1)
Counter 25 Hz (Bouncer free)
■■■ ■
Analog inputs (AI)
LG-Ni1000
■■■ ■
■
Pt 1000 / 0...2500 Ohm
■■■ ■ ■
T1
■■■ ■
DC O...10V
■■■ ■ ■
3)
4...20 mA / 0...20 mA
■■ ■
4)
Analog outputs (AO)
DC 0...10 V
■■■ ■
4...20 mA 5-8
2)
5-8
2)
Digital outputs (DO)
Continuous contact on/off
■
■
Continuous contact, 3-stage
■■
3-stage output
■■
Impulse on/off, 3-stage
■■
Multistate
■■
Triac-continuous contact
■
Triac-impulse (3-stage)
■
Triac-Pulsbreitenmodulation
■
Beleuchtungssteuerung, bistabil
■
All I/O points of a module are confi gurable on any, implemented functionality. The module TX1.OPEN enables the integration of Modbus, M-bus etc. via
RS232, 485 on the PXC50/100/200..D.
1)
On the TXM1.16D the counters are implemented only on the inputs 1 to 8
2)
On the TXM1.8X.. the current exists 4...20 mA are implemented only on the I/Os 5 to 8
3)
0...250 Ohm
4)
Pt100 4-wire