Data Sheet for Product
11/14
Siemens RDF300…/RDF340 / RDF400… / RDF600... Flush-mounted Room thermostats CE1N3076en
Smart Infrastructure 2020-02-21
Function input:
External temperature sensor, heating/cooling
changeover sensor, operating mode switchover
contact, dewpoint monitor contact, enable electrical
heater contact, alarm contact
Selectable
X1: P38
X2: P40
Switching differential, adjustable
Heating mode (P30)
Cooling mode (P31)
2 K (0.5...6K)
1 K (0.5...6K)
Setpoint setting and range
Comfort (P08)
Economy (P11-P12)
Protection
(P65
-
P66)
21°C (5...40 °C)
15°C/30°C (OFF, 5...40 °C)
8°C/OFF (OFF, 5...40 °C)
Multifunctional input X1/X2
Input X1
Input X2
Selectable 0…6
3: (P38) operating mode
switchover
2: (P40) heating/cooling
changeover sensor
Built-in room temperature sensor
Measuring range
Accuracy at 25 °C
Temperature calibration range
0…49 °C
< ± 0.5 K
±
3.0 K
Settings and display resolution
Setpoints
Cur
rent temp
er
ature value display
ed
0.5 °C
0.5 °C
Storage
Climatic conditions
As per IEC 60721-3-1
Class 1K3
Transport
Climatic conditions
As per IEC 60721-3-2
Class 2K3
Operation
Climatic conditions
As per IEC 60721-3-3
Class 3K5
1)
EU Conformity (CE) RDF3… CE1T3076_1
*)
RDF4… CE1T3076xx_2
*)
RDF600…
CE1T3076xx_3
*)
RCM Conformity RDF3…, RDF600… A5W90002894-A
*)
RDF600…
CE1T3076
en
-
C
*)
Degree of protection of housing
IP 30 to EN 60529
Protective class
II as per EN 60730
-
1
Pollutio
n
class
Normal
Housi
ng flammability class according to UL94
V
-
0
The product environmental declarations CE1E3076_1en (RDF3…)
*)
, A5W00085839A
(RDF300.02/VB)
*)
, CE1E3076_2en (RDF4…)
*)
, CE1E3076_4en (RDF600…)
*)
contain
data on environmentally compatible product design and assessments (RoHS
compl
i
a
nce, materials comp
osition, packaging, environmental benefit, disposal).
Connection terminals Solid wires or prepared
stranded wires
1 x 0.4…
1
.5 mm
2
Housing front color RAL 9003 white
RAL
9004
b
lack
Weight RDF3..., RDF4...
RDF6
00...
0.220 kg
0.150 kg
*) The documents can be downloaded from http://siemens.com/bt/download.
1) No condensation is allowed.
Operational data
Environmental
cond
i
tions
Standards and
directives
Environmental
compatibi
l
ity
General