Smart Infrastructure 2020-02-21
4.2 Commissioning
The room thermostats are delivered with a fixed set of applications.
Select and activate the relevant application during commissioning using one of the
following tools:
– Local DIP switch and HMI
– Synco ACS
– ETS
Set the DIP switches before snapping the front panel to the mounting plate, if you
want to select an application via DIP switches.
All DIP switches need to be set to "OFF" (remote configuration), if you want to
select an application via commissioning tool.
After power is applied, the thermostat resets and all LCD segments flash, indica-
ting that the reset was correct. After the reset, which takes about 3 seconds, the
thermostat is ready for commissioning by qualified HVAC staff.
If all DIP switches are OFF, the display reads "NONE" to indicate that application
commissioning via a tool is required.
Each time the application is changed, the thermostat reloads the factory setting for
all control parameters, except for KNX device and zone addresses!
Connect the Synco ACS or ETS tools to the KNX bus cable at any point for
commissioning:
ACS and ETS require an interface:
– Ethernet/LAN KNX interface (e.g. Siemens N148 / N146 / N152)
– OCI702 USB-KNX interface
An external KNX bus power supply is required if an RDF is connected directly to a
tool (ACS or ETS) via KNX interface.
Applications
DIP switches
Note:
Connect tool
Note: