Data Sheet for Product

18
Siemens
A6V12071353_en--_b
Smart Infrastructure
2021-12-15
Read
Write
Object no.
Object
Address (Decimal)
Register Length
Read Only (RO) or Read/Write (R/W)
Function code (HEX)
0x03---Read Holding Registers
0x04---Read Input Registers
0x06---Write Single Register
0x10---Write Multiple Registers
Multi-Bytes Access Group
Special Process
Default
Data Type (Decimal)
25
P06
0035
1
R/W
0x03
0x06 or
0x10
4
-
0
0 = Room temperature
1 = Setpoint
2 = BUS temperature
26
P08
0036
1
R/W
0x03
0x06 or
0x10
4
x50
21
5…40
27
P09
0037
1
R/W
0x03
0x06 or
0x10
4
x50
5
5 …P10 (P10 = 40 max.)
28
P10
0038
1
R/W
0x03
0x06 or
0x10
4
x50
35
(P09 = 5 min.) P09…40
30
P14
0040
1
R/W
0x03
0x06 or
0x10
4
-
0
0 = Unlock
1 = Setpoint & fan buttons
adjustment only
2 = Full lock
34
P27
0044
1
R/W
0x03
0x06 or
0x10
4
-
0
0 = Previous operating mode
1 = OFF
2 = ON (Normal mode)
35
P28
0045
1
R/W
0x03
0x06 or
0x10
4
-
1
0 = Disable
1 = Enable
41
P53
0051
1
R/W
0x03
0x06 or
0x10
4
-
3
1 = 1-speed
2 = 2-speed
3 = 3-speed
4 = 4-speed
5 = 5-speed
6 = 6-speed
7 = 7-speed
46
P71
0056
1
R/W
0x03
0x06 or
0x10
4
-
0
0 = Disable
1 = Reload start
47
P81
0057
1
R/W
0x03
0x06 or
0x10
5
-
247
1…247
48
P82
0058
1
R/W
0x03
0x06 or
0x10
5
-
2
1 = 9600 bps
2 = 19200 bps
3 = 38400 bps
4 = 57600 bps
49
P83
0059
1
R/W
0x03
0x06 or
0x10
5
-
0
0 = 1/8/E/1
1 = 1/8/O/1
2 = 1/8/N/1
3 = 1/8/N/2
50
P98
0060
1
R/W
0x03
0x06 or
0x10
5
-
1
0 = Disable
1 = Enable