Data Sheet for Product

10
Siemens
A6V12071353_en--_b
Smart Infrastructure
2021-12-15
Use + or - to change the time up to 23 hours with a 0.5 h increment or decrement re-
spectively.
Press () to confirm the change. The device automatically exits delay Off timer
mode or press ( ) to return to previous step.
Or press ( ) to exit delay Off timer mode without saving changes and to return to
Normal mode.
3. Cancellation of timer with delay Off mode
Cancel by setting the timer to 0 hour.
4. Viewing or editing of timer with delay Off mode
Press and hold down for more than 3 seconds to view the remaining time.
Use + or - to change the time and press () to confirm the new value.
The timer runs according to the new value.
Operating mode setting upon power failure
If the VRF HMI unit is disconnected from AC 230 V and reconnected, the unit returns to the
operating mode before powering failure if P27=0. If P27=1, the unit is in OFF mode. If
P27=2, the unit resumes Normal mode (ON).
Typical Modbus / VRF gateway configuration
The Modbus master function includes the following two:
1-to-1 Modbus/VRF gateway with Modbus master function (usually customized product
by gateway suppliers)